Wago Pro Installation Case Box With 240 Various Connectors
Description
Description
Description
Wago Pro Installation Box With 240 Assorted Wago Connectors in a Plastic Carry Case
A professional kit for comprehensive use of the Wago connectors.
Contents:-
- 40 x 222-412 4mm 2-Pole Lever Connector
- 40 x 222-413 4mm 3-Pole Lever Connector
- 20 x 222-415 4mm 5-Pole Lever Connector
- 40 x 773-102 2.5mm 2-Pole Push Connector
- 40 x 773-104 2.5mm 4-Pole Push Connector
- 10 x 773-106 2.5mm 6-Pole Push Connector
- 10 x 773-108 2.5mm 8-Pole Push Connector
- 20 x 224-101 2.5mm 2-Pole Lighting Connector
- 20 x 224-112 2.5mm 2-Pole Lighting Connector
222 Series Compact Connectors Solid, stranded and flexible conductors from 0.08 - 2.5mm² (4mm² fine stranded) cross sections can now be connected using the 222 Series connector.
773 Series Push-wire Connectors for Junction Boxes 773 Series connectors are suitable for solid and 7-stranded conductors for use in junction boxes.
224 Series Lighting Connectors The 224 Series connectors combine Push-Wire and CAGE CLAMP® technology, making them ideal for lighting applications.
FAQs
Should WAGO connectors be used in an enclosure?
In order to comply with the requirements of the 16th Edition of the IEE Wiring Regulations/BS7671, all connectors should be used in a suitable enclosure of material complying with the relevant glow-wire test requirements of BS 458-2.1. (Fire hazard testing for electrotechnical products). This will provide
mechanical protection for the connectors as well as protection against dust, damp and accidental damage. Although WAGO connectors are IP20 (finger touch) with Polyamide 6.6 housing for strength and durability.
Do they need to be fixed in an enclosure?
The junction box connectors do not have to be fixed down in the housing provided that the cables are secured on their way into the box. However, fixing provides a more secure and professional looking finish.
Does there need to be strain relief on the cable?
Yes, there should be strain relief on the cable. This could be the cable clipped outside the enclosure or cable glands within the enclosure to prevent the cables being pulled out of the connectors.
I'm used to screw connections - how secure is your clamping system?
The WAGO Cage Clamp? and PushWire clamping systems guarantee gastight, maintenance-free connections every time. Our connectors incorporating these proven technologies have been used in industrial and building services applications worldwide. The company's reputation is built on the high quality and proven performance of our products. For installers, this ensures complete peace of mind.
How do I release the conductor from the terminal?
All WAGO connectors are re-usable. PushWire conductors are removed by pulling the conductor and twisting the connector. Cage Clamp? connections are released by using a screwdriver or pushbutton/lever operation.
Do your connectors comply with British Standards?
BSI recognise and harmonise with IEC 60947, 60998 and 60999. These are European standards which relate to terminal blocks and connectors. All WAGO products conform to these standards and other international requirements.
What other standards do your connectors comply with?
WAGO sells its products worldwide and is therefore in constant contact with testing and approvals houses around the globe.
There's a small cavity in a ceiling, wall or floor. Can a terminal block be fitted without the need for an additional back box?
Yes. When installing backless equipment, such as a domestic style luminaire, it is possible for the enclosure to be formed or completed with building material considered to be non-combustible when tested to BS 476-4. (Fire tests on building materials and structures. Non-combustibility tests for materials). Where there is any doubt that the building material does not meet this standard, the electrical connections should be shielded from the fabric of the building by a suitable electrical back-box.